Lopi Revere Indoor Fireplace User Manual


 
Stove Installation (for qualified installers only) 9
© Travis Industries 100-01165 4040806
Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met (follow the
clearances for the type of fireplace being used - either masonry or zero-clearance).
Side
Wall
Combustible Mantel
Combustible Top Facing
Non-Combustible
Hearth
Facing
Masonry
Fireplace
Minimum Clearances
k
l
m
n
o
p
q
x
Sidewall to Insert
Side Facing
Top Facing
with mantel shield
Mantel to Insert
with mantel shield
Hearth (Front)
Hearth (Side)
Front of Insert
Extension onto Hearth
15"
13"
28-1/2"
20-1/2"
30-1/2"
22-1/2"
16"
8"
36"
10"
q
l
k
p
x
o
n
m
ZC (Metal)
Fireplace
30"
12"
12"
N/A
24"
N/A
16"
8"
36"
10"
Figure 3
Hearth Requirements
Must extend 16" in front of the insert and 8" on both sides (min. 26" deep by 40-1/4" wide)
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
Chimney must have a clay tile liner or a stainless steel liner (positive connection)
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert
Chimney height: 15' minimum; 33' maximum.
Entire fireplace, including chimney, must meet local building requirements