LG Electronics RVL469 Air Conditioner User Manual


 
CE1N2527E / 04.03.1999 Siemens Building Technologies
4/8 Landis & Staefa Division
To provide this function, connection of the RVL469 to ist partner unit via the data bus is
mandatory. Each RVL469 requires one partner unit.
Communication with other units also takes place via the data bus and facilitates:
Signalling of heat demand to the heat source
Exchange of locking and enforced signals
Exchange of measured values such as outside temperature, return temperature, flow
temperature and of clock signals
Communication with other devices
Reception of heat demand signals from the SYNERGYR OZW30 central unit (from
software version 3.0)
Exchange of error messages
Fault message in the event of sensor faults
Fault message in the event of data bus faults
Flow temperature alarm; adjustable is a period of time during which the flow temp-
perature may stay outside the set limits; a fault message is given when the time has
elapsed
Display of parameters, actual values, operational statuses and fault messages
Simulation of outside temperature
Relay test; all relays can be controlled manually
Sensor test; all measured values of the sensors can be displayed
Testing the contacts connected to terminals H1M and H2M
Outside temperature-dependent frost protection for the plant; a minimum flow tem-
perature is maintained, its setpoint and the response threshold can be adjusted
Pump overrun time to prevent buildup of heat
Periodic pump run (pump kick) to prevent seizing of the pump in the summer
Controller hours run meter
For more detailed information about technical features, functions and communication
with LPB, please refer to the following pieces of documentation:
Basic Info RVL470: CE1P2522E
Data sheet Basic System Data LPB: CE1N2030E
Data sheet LPB: CE1N2032E
The RVL469 is comprised of controller insert, which accommodates the electronics, the
power section, the output relays and - on the front - all operating elements, and the
base, which carries the connection terminals. The operating elements are located be-
hind a lockable transparent cover.
The operating instructions can be inserted in the transparent cover.
The controller insert is secured to the base with two screws, one of which can be
sealed. The cover can also be sealed.
The RVL469 can be fitted in three different ways:
Wall mounting (on a wall, in the control panel, etc.)
Rail mounting (on a standard DIN mounting rail)
Flush panel mounting (control panel door, etc.)
Buttons for selecting the required operating mode
Info button
Direct adjustment of the heating curve with the the little bar on the front of the unit
(only if analog setting is selected)
Knob for manual readjustment of the room temperature
Three buttons for manual operation and manual positioning commands
The entry or readjustment of all setting parameters, activation of optional functions and
reading of actual values and statuses is made according to the operating line principle.
An operating line with an associated number is assigned to each parameter, each actual
value and each function that can be selected.
One pair of buttons is used to select an operating line and one pair to readjust the dis-
play.
Communication
Fault messages and flow
temperature alarm
Other functions
Mechanical design
Analog operating
elements
Digital operating
elements