CE1N2527E / 04.03.1999 Siemens Building Technologies
2/8 Landis & Staefa Division
– Optimization functions
– Protective functions
– Remote control
– Commissioning aids
– Communication functions
When ordering, please give type reference
RVL469
. Partner unit, sensors, actuator and
valve and, if required, room unit must be ordered as separate items.
Suitable partner units are:
– RVL470 (data sheet CE1N2522E)
– RVL471 (data sheet CE1N2524E)
– RVL472 (data sheet CE1N2526E)
– RVL47 (data sheet CE1N2523E)
•
Flow and return temperature: all sensors with LG-Ni 1000
Ω
at 0 °C, for example:
– Clamp-on temperature sensor QAD22
– Immersion temperature sensors QAE22... and QAP21.3
•
Room temperature:
– Room unit QAW50
– Room unit QAW70
– Room temperature sensor QAA24
•
Outside temperature:
– Outside sensor QAC22 (Ni sensing element)
– Outside sensor QAC32 (NTC sensing element)
All electric and electrohydraulic actuators for three-position control made by Lan-
dis & Staefa can be used.
For the different types of actuators, refer to data sheets 4500…4599.
The controller is capable of communicating with:
– All units with LPB capability made by Landis & Staefa
– SYNERGYR OZW30 central unit (from software version 3.0)
Connection to an RVL47... partner unit is mandatory. The partner unit is defined by as-
signing an address. Each partner unit can be operated with only one RVL469.
The RVL469 ha one plant type preprogrammed: room heating with mixing zone, three-
position control acting on mixing valve.
B9
A6/B5
B7
BUS (LPB)
2527S01
E1
A6 Room unit QAW50 or QAW70 E1 Load (space)
B1 Flow sensor LPB Data bus
B5 Room sensor M1 Heating circuit pump
B7 Return sensor N1 Controller RVL469
B9 Outside sensor Y1 Mixing valve heating circuit
Other functions
Ordering
Equipment
combinations
Partner unit
Suitable sensors and
room units
Suitable actuators
Communication
Technical design
Working principle
Plant type