16
Mini-Split
Standard
Single Zone
Type
A/C
A/C
A/C
A/C
A/C
H/P
H/P
H/P
H/P
H/P
System Model #
LS090CE
LS120CE
LS180CE
LS240CE
LS302CE
LS090HE
LS120HE
LS180HE
LS240HE
LS302HE
Indoor
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
BTUs
9,000
11,500
18,000
22,500
28,000
9,800
11,500
19,500
22,500
28,000
Rated
Amps
7.0
10.5
8.6/9.5
11.5/12.5
14.5/15.6
10.5
10.5
11.5/12.5
11.5/12.5
14.5/15.6
MCA*
15
15
15
20
25
15
15
20
20
25
MOP**
15
25
20
30
30
25
25
30
30
30
Electrical Specifications
Outdoor
115
115
230/208
230/208
230/208
115
115
230/208
230/208
230/208
Voltage
All equipment single phase.
NOTE: Please see local electrical codes for proper wire specifications.
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
***For LS180HE, LS240CE/HE, LS302CE/HE
Wire Size
Minimum AWG 14-3
12-3***
Indoor/Outdoor Connecting Cable Minimum AWG 18-4
Mini Split
Standard
Single Zone
Type
A/C
A/C
A/C
A/C
A/C
H/P
H/P
H/P
H/P
H/P
System
Model #
LS090CE
LS120CE
LS180CE
LS240CE
LS302CE
LS090HE
LS120HE
LS180HE
LS240HE
LS302HE
Pipe size
Liquid Suction
1/4" 3/8"
1/4" 1/2 "
1/4" 1/2 "
1/4" 5/8"
1/4" 5/8"
1/4" 1/2"
1/4" 1/2 "
1/4" 5/8 "
1/4" 5/8"
1/4" 5/8"
BTUs
9,000
11,500
18,000
22,500
28,000
9,800
11,500
19,500
22,500
28,000
Additional
Refrigerant
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.35 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.35 oz./ft.
Max. length
each pipe
50'
50'
100'
100'
100'
50'
50'
100'
100'
100'
Max.
elevation
25'
25'
50'
50'
50'
25'
25'
50'
50'
50'
Refrigerant Line & Formula Specifications***
25' maximum
8' minimum
16.4' maximum
OIL TRAP
INDOOR UNIT
OUTDOOR UNIT
***Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the
interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g.
basement installations) have the following additional requirement:
For systems with elevation of 25 ft. (see chart above and figure A), refrigerant
lines must be oil trapped between 8 ft. and 16.4 ft. of elevation.
For systems with elevation of greater than 25 ft. (see chart above), refrigerant
lines must be oil trapped at least every 16.4 ft. of elevation.
MINI-SPLIT STANDARD SINGLE ZONE
ELECTRICAL & REFRIGERATION• QUICK REFERENCE
Figure A.
Example: 25 ft. maximum elevation.