Lennox International Inc. Zone Control Panel Heating System User Manual


 
Troubleshooting
DETECTING HVAC SYSTEM PROBLEMS
Symptom Possible Solution
Pressure switch open.
Consult condensing unit manual for possible cause.
Compressor is off due to internal overload protector.
Consult condensing unit manual for possible cause.
Condenser control board anti short cycle timer is not
yet expired. Most anti short cycle timers are 5 minutes
or less, if the unit does not start after 5 minutes consult
the condensing unit manual for possible causes.
Limit on furnace open. Check position of DAS in
the plenum and move further down stream if possible.
High static condition must be corrected.
DAS limit jumper needs to be moved to a lower setting.
Trouble shoot air handler see air handler
documentation.
Condensing unit receiving signal but will not turn on.
Air handler receiving signal but will not turn on.
Page 10
A high static condition exists. Move the sensor
further down stream to sense air that has mixed more
thoroughly. Be sure not to place the senor past
the take offs. High static pressure must be corrected.
Bypass tap is too close to inlet of air handler.
Adjust bypass tap in the return air duct so that is further
away from the furnace. This will give the air more of a
chance to be tempered with room return air before
entering the air handler again.
Furnace tripped the primary limit, but the
zone panel does not indicate that the discharge
air limit has been exceeded.