Lennox International Inc. CBX32MV06 Thermostat User Manual


 
506920−01 09/12
Page 40
Table 3. Adjustable Parameters Table (Installer)
Parameter Name Default Min. Max. Incr. Dependency Note Installer entry
FURNACE
Heating indoor blower OFF delay DIP SW 60 180 10 None DIP switch setting in
Non−comm.
Heating indoor blower ON delay 45 sec 15 45 5 None 45 sec fixed in Non−
Comm. IFC
Cooling indoor blower OFF delay 0 sec 0 30 2 Outdoor Unit
present
Not used on Non
Comm. IFC
Cooling indoor Blower ON Delay 2 sec 0 10 1 Outdoor Unit
present
2 sec fixed in Non−
Comm. IFC
Heat pump indoor blower OFF delay 45 sec 0 60 5 Heat Pump present Not used on Non
Comm. IFC
Heat pump indoor blower ON delay 0 sec 0 30 5 Heat Pump present Not used on Non
Comm. IFC
Gas Heat Airflow Settings
Heating Airflow Control Type (variable
capacity furnaces only)
0 – Fixed
CFM
0 1 1 DATS installed
0 (Fixed CFM)
1 (Fixed DAT)
Low Heating Airflow (CFM @ min.
heat)
DIP SW
See furnace docu-
mentation (IOM or
engineering hand-
book) for size spe-
cific information
25
Heating Airflow
Control Type = 0
See furnace documen-
tation (IOM or engineer-
ing handbook) for size
specific information
High Heating Airflow (CFM @ 100%
heat)
DIP SW
25
Low Heating Discharge Air
Temperature (DAT @ min heat)
(variable capacity furnaces only)
DIP SW* 5
Heating Airflow
Control Type = 1
High Heating Discharge Air
Temperature (DAT @ 100% heat)
(variable capacity furnaces only)
DIP SW* 5
* − Default DAT value is rounded to the closest number on 5 deg F resolution and limited by Minimum and Maximum value.
table continued on next page