Lennox International Inc. CBX32MV06 Thermostat User Manual


 
icomfort Wi-Fit 7−Day Programmable Communicating Thermostat
Page 39
Table 3. Adjustable Parameters Table (Installer)
Parameter Name: Installer entryIncrementParameter Value SettingDefault
AIR HANDLER
Equipment Name Air Handler (keyboard input screen) Ċ
Electric Heating Airflow
nnnn CFM
(See Note 3 at
end of table)
NOTE: CFM Default and Values Settings are depen-
dent on the tonnage of the unit
5CFM
Low Cooling Airflow 5CFM
High Cooling Airflow 5CFM
Cooling Airflow Profile 1
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min; OFF:50%/30s
Ċ
Low Heating Airflow
nnnn CFM
(See Note 3 at
end of table)
NOTE: CFM Default and Values Settings are depen-
dent on the tonnage of the unit
5CFM
High Heating Airflow 5CFM
Continuous Indoor Blower Airflow 10CFM
Humidification Airflow 10CFM
Dehumidification Airflow 70%
60 to 80% (percentage of reduction of High Cooling
Airflow)
1%
Delays:
Heating Indoor Blower OFF
10 sec 0 to 10 Seconds 1 sec
Heating Indoor Blower ON 0 sec 0 to 5 Seconds 1 sec
Cooling Indoor Blower OFF 0 sec 0 to 30 Seconds 2 sec
Cooling Indoor Blower ON 2 sec 0 to 10 Seconds 1 sec
HP Indoor Blower OFF 45 sec 0 to 60 Seconds 5 sec
HP Indoor Blower ON 0 sec 0 to 30 Seconds 5 sec