Lennox Hearth Villa Vista Indoor Fireplace User Manual


 
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
14
The duct system must be installed respecting
the following:
1. Remove the top and bottom plates closing up
the 8" diameter holes on top of the fireplace.
Then, cut the insulation in order to obtain two
8" diameter openings. Fix the adaptors on
the fireplace openings by turning clockwise
(refer to Figures 16 and 17).
2. Maintain at least a 2" (50mm) clearance
between the ducts and any combustible
material; the required hole size is 13" x 13"
(330 mm x 330 mm).
Exception: For the grills, the framing can
be 10-3/4" x 10-3/4" (275 mm x 275 mm)
to provide the clearance as required by the
integral spacers on the double outlet duct
system.
3. The maximum number of elbows in a run
of duct is two.
4. Maintain at least 6-1/2" (160 mm) clearance
from the outlet grill framing to a combustible
ceiling, side wall or mantel.
5. When traversing a combustible wall or floor,
a firestop must be installed at the wall or
floor penetration. The hole size must be
13" X 13". (330 mm x 330 mm).
6. Do not connect the hot air ducts to a central
heating system. Malfunction of the heating
system’s fan will cause the furnace duct to
overheat. A furnace duct is only single wall
and not double wall as is required for the
Villa Vista™ fireplace hot air exhaust.
7. Use only Lennox Hearth Products grills and
components as described in this manual.
Other grills or registers, for example, may be
too restrictive and may overheat the fireplace
or ceiling.
8. Do not use insulated flexible ducts as they
will overheat.
FIRESTOP
ATTIC RADIATION
SHIELD
ROOF-SUPPORT
FLASHING
COLLAR
RAIN CAP
NON-COMBUSTIBLE
FACING
*54"MIN.
68"MIN.
*48" WHEN CLEAN FACE
PANEL (BPCF) IS INSTALLED
(AS SHOWN)
Figure 18
11. The hot air outlet grills must be installed with
the louvers pointing downwards in order to
prevent overheating adjacent ceilings.
12. Do not install outlet grills facing upward in
a floor. They will get hot and create a risk
of burns if stepped on.
9. Do not use tees or any other components
than the ones specifically listed here.
10. All ducts must extend upwards or hori-
zontally. Never try to route the ducting
downwards.
u
Combustibles are not allowed on the black portion of the fireplace. Drywall can be installed
below the top spacer up to the fireplace.
u