Kidde i12060 Smoke Alarm User Manual


 
3. INSTALLATION INSTRUCTIONS
WIRING REQUIREMENTS
This smoke alarm should be installed on a U.L. listed or recognized junction
box. All connections should be made by a qualified electrician and all wiring
used shall be in accordance with articles 210 and 300.3(B) of the U.S. National
Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdic-
tion in your area. The multiple station interconnect wiring to the alarms must
be run in the same raceway or cable as the AC power wiring. In addition, the
resistance of the interconnect wiring shall be a maximum of 10 ohms.
The appropriate power source is 120 Volt A.C. Single Phase supplied from a
non-switchable circuit which is not protected by a ground fault interrupter.
WARNING: This alarm cannot be operated from power derived from a square
wave, modified square wave or modified sine wave inverters. These types of
inverters are sometimes used to supply power to the structure in off grid
installations, such as solar or wind derived power sources. These power
sources produce high peak voltages that will damage the alarm.
WIRING INSTRUCTIONS FOR A.C. QUICK CONNECT HARNESS
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING
THE ALARM.
For alarms that are used as single station, DO NOT CONNECT THE RED WIRE
TO ANYTHING. Leave the r
ed wire insulating cap in place to make certain that
the red wire cannot contact any metal parts or the electrical box.
When alarms are interconnected, all interconnected units must be powered
from a single circuit.
A maximum of 24 Kidde devices may be interconnected in a multiple station
arrangement. The interconnect system should not exceed the NFPA intercon-
nect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon
monoxide, etc.). With 18 alarms interconnected, it is still possible to intercon-
nect up to a total of 6 remote signaling devices and/or relay modules.
When mixing models which have battery backup (i12040, i12060, i12080,
1275, 1276, 1285, 1296, PE120, PI2000, KN-COSM-IB, RF-SM-ACDC,
HD135F, KN-COB-IC, KN-COP-IC) with models without battery backup, (i1220,
1235, KN-COSM-I, KN-COB-ICB, KN-COP-ICB, 120X, SM120X,CO120X,
SL177i) be advised that the models without battery backup will not respond
during an AC power failure.
For more information about compatible interconnect units and their function-
ality in an interconnect system, visit our web site at: www.Kidde.com