Kidde SL177 Smoke Alarm User Manual


 
4. The maximum wire run distance between the first and last device in an inter-
connect system is 1000 ft.
5. Figure 1 illustrates interconnection wiring. Improper connection will result in
damage to the strobe light or alarms, failure to operate, or a shock hazard.
6. Make certain that all devices in the interconnect system are wired to a contin-
uous (non-switched, non-GFI or GCFI protected) power line.
FIGURE 1: INTERCONNECT WIRING DIAGRAM FOR SL177i.
WIRE ON STROBE LIGHT HARNESS CONNECTED TO:
BLACK . . . . . . . . . .HOT SIDE OF AC LINE
WHITE . . . . . . . . . .NEUTRAL AC LINE
RED . . . . . . . . . . . .INTERCONNECT LINES (RED WIRES) OF THE OTHER UNITS
IN THE MULTIPLE STATION SET UP
N
L
WIRE NUT
OR
EQUIVALENT
WHITE
BLACK
RED
WHITE
RED
BLACK
WHITE WHITE
RED
RED
BLACK
BLACK
FUSE OR CIRCUIT BREAKER
SMOKE ALARM
STROBE LIGHT
HEAT ALARM
CO ALARM
FIGURE 1
BLACK
WIRE NUT OR
EQUIVALENT
WHITE
FUSE OR CIRCUIT BREAKER
SWITCHING DEVICE USED
TO CONTROL THE
OPERATION OF THE
SL177 STROBE LIGHT
FIGURE 2