Kidde SL177 Smoke Alarm User Manual


 
Multiple station (24) interconnect unit, interfaces directly with Kidde
Safety:
Ion Smoke Alarm Models: 1235, 1235CA, 1275, 1275CA, 1276,
1276CA, 1285, 1285CA, 1296, i12020,
i12020CA, i12040, i12040CA, i12060,
i12060CA, i12080, RF-SM-ACDC
Photo Smoke Alarms: PE120, PE120CA,
Photo / Ion Smoke Alarms: PI12000, PI2000CA
Heat Alarm Models: HD135F, HD135FCA
CO / Ion Smoke Alarm Models: KN-COSM-I, KN-COSM-IB, KN-COSM-ICA,
KNCOSM-IBCA
Carbon Monoxide Alarms Models: KN-COB-IC, KN-COB-IC-CA,
KN-COB-ICB-CA, KN-COP-IC, KN-COP-IC-CA
Flash Rate (smoke alarm event): Constant 1 flash per second nominal
Flash Rate (CO alarm event): Intermittent 1 flash per second nominal
(approximately 4 flashes, followed by
approximately 5 seconds OFF)
Model Number: SL177 ( 2 WIRE DIRECT CONNECT UNIT )
Electrical Rating: Special Application 110-130 VAC
Maximum Operating RMS Current 389 mA
Note: This device was only tested over the range 110-130 VAC. Do not take
80% and110% of these ratings into account during installation as this was not
tested for.
Flash Rate: Constant 1 flash per second nominal
Model Number: SL177i & SL177
Temperature Limits: 32˚F (0˚C) TO 120˚F (49˚C)
Mounting: Wall or Ceiling
Applications: Primary Direct or Indirect and Supplementary
Light Output: 177 Candela minimum (on axis
measurement)