Johnson Controls TCGD30 Air Conditioner User Manual


 
415571-UTG-C-0309
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.
Physical and Electrical Data
MODEL
TCGD30
S43S1
TCGD36
S43S1
TCGD42
S43S1
TCGD48
S43S1
TCGD60
S43S1
TCGD30
S44S1
TCGD36
S44S1
TCGD42
S44S1
TCGD48
S44S1
TCGD60
S44S1
Unit Supply Voltage 208-230V, 3 60Hz 460V, 3 60Hz
Normal Voltage Range
1
187 to 252 432 to 532
Minimum Circuit Ampacity 11.4 12.3 16.3 15.5 23.9 9.4 7.1 8.0 7.9 13.5
Max. Overcurrent Device Amps
2
15 20 25 25 40 15 15 15 15 20
Min. Overcurrent Device Amps
3
15 15 20 20 25 15 15 15 15 15
Compressor Type Recip Recip Recip Recip Scroll Recip Recip Recip Recip Scroll
Compressor Amps
Rated Load 8.1 8.6 11.8 11.2 17.9 6.6 4.5 5.2 5.1 9.6
Locked Rotor 63 68 88 88 120 30 34 44 44 70
Crankcase Heater No No No No No No No No No No
Fan Motor Amps Rated Load 1.2 1.5 1.5 1.5 1.5 1.2 1.5 1.5 1.5 1.5
Fan Diameter Inches 17.5 22 22 22 22 17.5 22 22 22 22
Fan Motor
Rated HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Nominal RPM 1100 850 850 850 850 1100 850 850 850 850
Nominal CFM 2050 3200 2950 2950 3600 2050 3200 2950 2950 3600
Coil
Face Area Sq. Ft. 9.6 13.07 14.16 14.16 18.68 9.6 13.07 14.16 14.16 18.68
Rows Deep 1 1 1 1 1 1 1 1 1 1
Fin / Inches 23 23 23 23 23 23 23 23 23 23
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 7/8 7/8 7/8 3/4 3/4 7/8 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
3 - 14 4 - 9 4 - 5 4 - 9 5 - 6 3 - 14 4 - 9 4 - 5 4 - 9 5 - 6
Charge Per Foot, Oz. 0.62 0.62 0.67 0.67 0.67 0.62 0.62 0.67 0.67 0.67
Operating Weight Lbs. 131 145 173 173 195 131 145 173 173 195
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or
subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25 feet, you may refer to publications
software 036-68001-001 for proper line sizing.
B
A
C
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B C Liquid Vapor
30 28 23-1/2 23-1/2
3/8”
3/4”
36 28 29 29
42 30 29 29
7/8”48 30 29 29
60 32 33-5/8 33-5/8