Johnson Controls TCGD18 THRU 60 Air Conditioner User Manual


 
Subject to change without notice. Published in U.S.A. 359319-BTG-G-0509
Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 359319-FTG-F-0309
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD60S41S1
INDOOR COIL MODEL NO. FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1600 1800 2000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 55.8 63.8 62.1 65.2 71.9 60.3 65.7 62.8 66.7 69.8 64.8 67.5 63.5 68.2 67.8
S.C. 54.7 51.6 41.4 41.1 34.1 58.4 54.2 43.9 42.6 31.9 62.1 56.8 46.5 44.2 29.6
KW 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.1 3.0 3.1 3.1
75
T.C. 56.9 61.1 58.9 62.7 69.7 59.2 63.0 59.9 64.3 67.9 61.4 64.9 61.0 65.9 66.0
S.C. 53.9 50.4 40.5 40.0 33.5 55.8 53.1 43.1 41.8 31.5 57.7 55.7 45.6 43.6 29.5
KW 3.4 3.5 3.5 3.5 3.6 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
85
T.C. 58.0 58.4 55.7 60.3 67.6 58.0 60.4 57.1 61.9 65.9 58.1 62.4 58.5 63.6 64.1
S.C. 53.2 49.3 39.7 39.0 32.9 53.3 52.0 42.2 41.0 31.2 53.4 54.7 44.8 42.9 29.4
KW 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0
95
T.C. 59.1 55.7 52.5 56.9 65.5 56.9 57.8 54.3 57.0 63.9 54.7 59.8 56.0 61.2 62.2
S.C. 52.4 48.1 38.8 37.9 32.3 50.7 50.9 41.4 38.8 30.8 49.0 53.6 43.9 42.3 29.4
KW 4.3 4.3 4.3 4.4 4.5 4.3 4.3 4.3 4.4 4.4 4.3 4.3 4.3 4.4 4.4
105
T.C. 56.4 52.2 48.8 54.0 60.1 54.0 54.3 50.5 55.7 59.7 51.6 56.3 52.2 57.4 59.4
S.C. 49.7 45.9 37.5 36.5 29.7 47.9 48.3 40.0 38.7 29.4 46.2 50.6 42.5 40.9 29.0
KW 4.9 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0 5.0 4.9 4.9 4.9 5.0 5.0
115
T.C. 53.8 48.8 45.2 50.2 54.8 51.2 50.9 46.8 51.9 55.7 48.7 53.0 48.5 53.6 56.6
S.C. 47.1 43.8 36.2 35.0 27.3 45.3 45.7 38.6 37.3 27.9 43.5 47.7 41.1 39.6 28.6
KW 5.5 5.4 5.4 5.5 5.6 5.5 5.5 5.4 5.5 5.6 5.4 5.5 5.4 5.5 5.6
125
T.C. 51.2 45.4 41.6 46.5 49.4 48.5 47.5 43.2 48.2 51.6 45.7 49.7 44.8 49.8 53.8
S.C. 44.5 41.7 34.9 33.6 24.9 42.6 43.2 37.3 35.9 26.5 40.7 44.7 39.7 38.3 28.2
KW 6.1 6.0 5.9 6.1 6.2 6.0 6.0 6.0 6.1 6.2 6.0 6.0 6.0 6.1 6.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers Coils T.C. S.C. KW
FC/MC62 1.00 1.00 1.00
HC60 1.00 1.00 1.00
UC60 1.00 1.00 1.00
AHP/SHP60 1.00 1.00 1.00
AHX60 1.00 1.00 0.98
AV/SV*60 1.00 1.01 1.00
MV20D FC/MC60D 1.00 1.01 1.00
MA20D FC/MC60D 1.00 1.00 1.00
MV20D FC/MC62D 1.00 1.01 1.00
MA20D FC/MC62D 1.00 1.00 1.00
F5FP060 1.00 1.00 1.00
F6FP060 1.00 1.00 0.96
F4FV060 – 1.00 1.00 0.99
Furnaces Coils T.C. S.C. KW
T*(8,L)X*C16 FC/PC60C 0.99 0.98 0.99
T*(8,L)X*C20 FC/MC/PC60D 1.00 0.98 1.00
T*9X*C16 FC/PC60C 0.98 0.98 0.98
T*9X*C20 FC/PC60C 0.98 0.98 0.98
T*9X*D20 FC/MC/PC60D 0.99 0.98 0.99
T*9X*C20 FC/MC/PC60D 0.99 0.98 0.99
T*(8,L)X*C20 FC/MC62D 1.00 0.98 1.00
T*(8,L)X*C16 UC60C 0.98 0.97 0.98
T*(8,L)X*C20 UC60D 0.99 1.00 0.99
T*9X*C16 FC/PC60C 0.98 0.97 0.98
T*9X*C20 FC/PC60C 0.98 0.97 0.98
T*9X*D20 UC60D 0.98 0.97 0.98
T*(8,L)X*C20 UC60D 0.99 1.00 0.99
T*9X*C20 UC60D 0.98 0.97 0.98
(T*9C/T*9V)*D20 FC/MC/PC60D 0.97 0.95 0.96
T*(8,L)C*C20 FC/MC62D 0.99 0.97 0.94
(T*9C/T*9V)*C20 FC/MC62D 0.98 0.96 0.97
(T*9C/T*9V)*D20 FC/MC62D 0.99 0.96 0.96
T*(8,L)C*C20 FC/PC60C 0.98 0.96 0.94
(T*9C/T*9V)*C20 FC/PC60C 0.97 0.95 0.96
(T*9C/T*9V)*D20 HC60 0.94 0.93 0.95
T*(8,L)C*C20 UC60C 0.95 0.91 0.93
(T*9C/T*9V)*C20 UC60C 0.94 0.90 0.96
(T*9C/T*9V)*D20 UC60D 0.94 0.90 0.95