John Deere AC-375LP Electric Heater User Manual


 
10 Operator’s Manual
Preparation
VENTILATION
WARNING: FOLLOW THE MINIMUM FRESH, OUTSIDE
AIR VENTILATION REQUIREMENTS. IF PROPER
FRESH, OUTSIDE AIR VENTILATION IS NOT
PROVIDED, CARBON MONOXIDE POISONING
CAN OCCUR. PROVIDE PROPER FRESH, OUTSIDE
AIR VENTILATION BEFORE RUNNING HEATER.
Provide a fresh air opening of at least three square feet for
each 100,000 Btu/Hr rating. Provide extra fresh air if more
heaters are being used.
PROPANE SUPPLY
Propane / L.P. gas and Propane / L.P. tank(s) are to be
furnished by the user.
Use this heater only with a propane vapor withdrawal
supply system. See Chapter 5 of the Standard for Storage
and Handling of Liquefied Petroleum Gas, ANSI/NFPA 58
and the Propane Installation Code CAN/CGA B149.2. Your
local library or fire department will have this booklet.
The amount of Propane / L.P. gas ready for use from
Propane / L.P. tanks varies. Two factors decide this amount:
1. The amount of Propane / L.P. gas in tank(s)
2. The temperature of tank(s)
The chart below shows the number of 100 pound (45
kg) tanks needed to run this heater. Do not operate this
product with any tanks smaller than 100 pounds.
Less gas is vaporized at lower temperatures. You may
need two or more 100 pound (45 kg) tanks or one larger
tank in colder weather. Your local propane gas dealer will
help you select the proper supply system. The minimum
surrounding air temperature rating for each heater is
-20° F (-29° C).
Temperature at Tank # of Tanks
40°F (5°C) and above 3
Below 40°F (5°C) (Use larger tank)