Honeywell V4944 Thermostat User Manual


 
PRODUCT DATA
65-0214-08
V4943/V8943B,C,N;
V4944/V8944B,C,L,N
Regulating Diaphragm Gas Valves
APPLICATION
The V4943/V8943B and N (single stage) and V4944/V8944B
and N (two stage) are solenoid-operated diaphragm valves
suitable for natural gas only. The V4943/V8943C and
V4944/V8944C and L are solenoid-operated diaphragm
valves suitable for Liquefied Petroleum (LP) gas only. These
valves are used on boilers, unit heaters, duct furnaces,
makeup air and rooftop heaters.
FEATURES
Models are available for natural or liquid petroleum
(LP) gases.
Valve models L, N are rapid opening (less than six
seconds) and fast closing, and are available for LP and
natural gases, respectively.
Line voltage with two-wire thermostat or controller is
used with V4943; V8943 is used with 24V thermostat or
controller.
V4944 is used with line voltage dual-stage thermostat
or controller; V8944 is used with 24V dual-stage
thermostat or controller.
Slow opening B,C valve models are available for
natural and LP gases respectively.
Valve closes on power failure; recommended for final
shutoff service.
Valve closing time: 2 seconds maximum at 7 inches wc
inlet pressure.
Valves rated for 0.5 pound per square inch (psi) (3.4
kPa).
Leadwires and cover for electrical conduit connections
are provided.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 6
Operation .......................................................................... 9
Checkout and Troubleshooting ......................................... 10
Service Information .......................................................... 12