Honeywell TH8110 Thermostat User Manual


 
VisionPRO
TM
8000 Touchscreen Programmable Thermostat
68-0280—01 10
Fig. 20. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).
Fig. 21. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).
R
Y
G
C
Y2
L
E
SI
H
EAT P
U
M
P
COMPRESSOR
RELAY
M19905
CHANGEOVER
VALVE
FAN RELAY
HEAT 2 RELAY
(AUXILIARY HEAT)
R
C
1
1
2
2
3
4
5
6
6
6
4
5
5
OPTIONAL 24 VAC
CO
MM
O
N
CO
NNE
C
TI
ON
EQUIPMENT
MONITOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS
A 24 VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
EMERGENCY
HEAT RELAY
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
R
Y
G
C
Y2
L
E
SI
H
EAT P
U
M
P
COMPRESSOR 2 COMPRESSOR 1
M19906
CHANGEOVER
VALVE
FAN RELAY
HEAT 2 RELAY
(AUXILIARY HEAT)
R
C
1
1
2
2
3
4
5
6
6
6
3
5
5
OPTIONAL 24 VAC
CO
MM
O
N
CO
NNE
C
TI
ON
EQUIPMENT
MONITOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS
A 24 VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
EMERGENCY
HEAT RELAY
4
OUTDOOR/INDOOR
TEMPERATURE
SENSOR