PRO TH3110D Non-programmable Digital Thermostat
9
10
0
Test
10
30
70
Heating system
Cooling system
Thermostat
information
(for reference only)
0 Heat and fan turn off.
1 Heat turns on. Fan also turns on immediately if Fan Operation
Switch is set to Electric Heat/Heat Pump (see page 6).
0 Compressor and fan turn off.
1 Compressor and fan turn on.
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System Test System Status
Installer system test
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
System switch
System test
number
System status
1 Set
SSYYSSTTEEMM
switch to Cool.
2 Press to turn on cooling system, then check system status (see table, below).
3 Press to turn off cooling system.
4 Set
SSYYSSTTEEMM
switch to Heat.
5 Press to turn on heating system, then check system status (see table, below).
6 Press to turn off heating system.
7 [Optional] Set
SSYYSSTTEEMM
switch to Off to display thermostat information (see table, below).
Press to display 71-76.
8Press and hold to terminate system test at any time.
Follow the procedure below to test the heating and cooling system.