BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
17 63-4523—01
Standard Object Types Supported
Table 6. Standard Object Types Supported
a
The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value if written is not
derived from the application level of the thermostat.
• Room Humidity (AV11)
• PI Heating Demand (AV20)
• PI Cooling Demand (AV21)
• Economizer Output (AV22)
• Eff Reset Humidification RH Spt (AV96)
• Humidifier Output (AV101)
b
Object_Name property is writable for 1 object only :
• Room_Temperature (AV7)
Proprietary Properties
Table 7. Proprietary Properties
Object Type
Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported
Writable Properties
Analog Input
Reliability Out_of_Service
Analog Value Reliability
Present_Value
a
Out_of_Service
a
Object_Name
b
Binary Input
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group N/A N/A
Multi-state Value
Reliability
States_Text
Present_Value
Out_of_Service
Schedule Weekly_schedule
Present_Value
Weekly_Schedule
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString
The version number of the BACnet communications
module. This is the hardware version number.
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration value.
The range is –5.0 deg F to 5.0 deg F for a temperature
and –15% to 15% for humidity.