Honeywell TB7600 Thermostat User Manual


 
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
63-4523—01 16
Economizer
Changeover Setpoint
AV 77 Present_Value (R,W) √√
Economizer Minimum
Position
AV 78 Present_Value (R,W) √√
Mechanical Cooling
Enabled
BV 79 Present_Value (R,W) √√
Mixed Air Setpoint AV 80 Present_Value (R,W) √√
Heatpump Model
Configuration Options
GRP 81 Present_Value (R)
High Balance Point AV 82 Present_Value (R,W) √√
Low Balance Point AV 83 Present_Value (R,W) √√
Comfort Mode BV 84 Present_Value (R,W) √√
Reversing Valve
Configuration
BV 85 Present_Value (R,W) √√
Compressor Interlock BV 86 Present_Value (R,W) √√
Dehumidification Model
Configuration Options
GRP 87 Present_Value (R)
RH Display BV 88 Present_Value (R,W) √√
Dehumidification RH
Setpoint
AV 89 Present_Value (R,W) √√
Dehumidification
Hysterisys
AV 90 Present_Value (R,W) √√
Dehumidification Low
OA Lockout
AV 91 Present_Value (R,W) √√
Dehumidification
Lockout Functions
BV 92 Present_Value (R,W) √√
Dehumidification Output
Status
BI 93 Present_Value (R) √√
Humidification Model
Configuration Options
GRP 94 Present_Value (R)
Humidification RH
Setpoint
AV 95 Present_Value (R,W) √√
Eff (Effective) Reset
Humidification RH Spt
(Setpoint)
AV 96 Present_Value (R) √√
Humidification High
Limit Spt (Setpoint)
AV 97 Present_Value (R,W) √√
Low RH Setpoint AV 98 Present_Value (R,W) √√
Low Temp Reset RH
Setpoint
AV 99 Present_Value (R,W) √√
High Temp Reset RH
Setpoint
AV 100 Present_Value (R,W) √√
Humidifier Output AV 101 Present_Value (R) √√
Local Schedule SCH 102 Present_Value (R,W) √√√√√
Table 5. Objects
Object Name
Type and
Instance
Object Property
TB7600A5x14B
TB7652A5x14B
TB7600B5x14B
TB7652B5x14B
TB7605B5x14B
TB7656B5x14B
TB7607B5x14B
TB7657B5x14B
TB7600H5x14B
TB7652H5x14B