Honeywell T8611M Thermostat User Manual


 
T8611M DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
9 69-1415—1
Fig. 12. Display of all LCD segments.
Fig. 13. Display of test number.
Refer to Table 5 for the directions and results of the
specific tests.
NOTE: Press Time to advance to the next test and
Time to go back to the previous test. Press
Run Program to exit the System Test,
Table 5. Installer System Test Options.
NOTE: Press any key and the displayed numbers change. Press Time to go to the previous test and Time to go to
the next test. The Run Program key does not exit this test. Press Time or Time and then the
Run Program key to exit.
M14559
Aux Ht
Set Day/TimeSet Program
Mon
Wake Leave Return Sleep
OutdoorRoom
Filter
Wait
System
Fan
Em Heat
On
Auto
Off
Cool
Auto
AM
PM
Hold for
Heat
Cool
Repl Batt
Recovery
DST
TueWedThu Fri Sat Sun
Days
Temporary Setting
Em Ht
M1461
2
Keys to
Press
Test
Number Description
Heating Equipment System Test
Time 10 Enter heating equipment system test.
s
11 Stage one heat comes on. The system fan is also energized.
s
12 Stage two heat comes on. Stage one heat and system fan remain on.
s
13 Stage three heat comes on. Stage one and two remain on.
t
12 Stage three heat turns off.
t
11 Stage two heat turns off.
t
10 Stage one heat and system fan turn off.
Emergency Equipment Heating Equipment System Test
Time 20 Change from heating to emergency heating equipment system test.
s
21 Emergency heat comes on.
s
22 Stage two emergency heat comes on.
s
21 Stage two emergency heat turns off.
t
20 Emergency heat turns off.
Cooling Equipment System Test
Time 30 Change from heating or emergency heating to cooling equipment system test.
s
31 Cool and system fan come on.
s
32 Stage two cooling comes on.
t
31 Stage two cooling turns off.
t
30 Cool and system fan turn off.
Fan Equipment System Test
Time 40 Change from cooling to fan equipment system test.
s
41 Fan comes on.
t
40 Fan turns off.
Key Operation System Test
Time 60 Change from fan to key operation system test.