Honeywell T8090A/191108A Thermostat User Manual


 
69-0574—2 18
Troubleshooting
(continued)
Problem Check Action
No cooling 1
(continued)
condenser switch position.
Located outdoors and may be
turned OFF.
Move to ON position.
thermostat connections. Check
for correct terminal hookups.
Repair any frayed or broken wires.
Firmly tighten all terminal screws.
Turn OFF power to cooling system.
other. Contact a qualified service technician for
assistance.
Thermostat setting
and thermometer
level position of thermostat. Reinstall thermostat wallplate or subbase.
Use a spirit level.
reading disagree.
area around thermostat for drafts
or radiant heat.
Thermostat should be about 5 ft (1.5m)
above floor on an inside wall. Contact
qualified service technician for change of
location.
(continued)