Honeywell SDC Thermostat User Manual


 
Operation SDC / DHC
54 EN2H-0220GE51 R0308
4.2.3.3.3 Individualised operating mode for each heating circuit
Each heating circuit can be assigned an individualised operating
mode.
Press button.
Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button
î.
Confirm selected circuit by pressing the input button
î.
Select flashing operating mode by turning the input button
î.
Confirm set operating mode by pressing the
button or the
input button
î.
With short-term operating modes (ABSENT, PARTY), set
desired target value by turning the input button
î and confirm
set value by pressing the input button
î.
Alternative: Automatic acceptance of the value after the set
information time (see 4.1.2.7 "System information" button, pg. 26).
Pos: 50 /156 -Honeywel l/Bedi enung/So mmer_He izgrenze @ 1\m od_12076 4705824 4_6.doc @ 9900
4.2.3.4 Summer / Heating limit
This parameter specifies the end of heating operation depending
on the outside temperature based on the following criteria:
Quick increase in outside temperature
If the averaged outside temperature is below the set value and
the current outside temperature is 2 K above the set value,
heating operation is interrupted.
Slow increase in outside temperature
Deactivation is also initiated when the averaged and current
outside temperature exceeds the set value.
Setting
C