R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
3 65-0109—8
Table 2. Flame Detection Systems.
a
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES Relay Module.
b
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.
c
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation
and shuts down burner if detection system fails.
d
Use only Honeywell part no. 38316 Photocell.
e
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
f
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies to
R7847C series 3 or greater; R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.
g
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use C7012E,F
Flame Detector with R7847C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A
Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for twenty-four hours or longer.
h
R7847A,B Amplifiers with 0.8/1 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
i
R7824C Series 2 and greater and R7847C Series 4 and greater check flame detector system when flame reaches 1.5 Vdc or at 4.5
seconds, whichever occurs first.
j
Order flame rod separately; see flame detector Instructions for holder.
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Type Color Self-Checking Model
Flame
Failure
Response
Time (sec)
a
Fuel Type Models
Rectification Green Dymanic Self-
Check
R7824C
b,c, i
3 Gas, oil,
coal
Ultraviolet (Purple
Peeper®)
C7024E,F
No
R7847A
h
0.8/1 or 2/3 Gas Rectifying Flame Rod
Holders
j
C7004, C7007, C7011
Complete Assemblies:
C7008, C7009, Q179
No
R7847A
h
0.8/1 or
2/3
Oil Rectifying Photocell C7003, C7010, C7013,
C7014
d
No
R7847A
h
2/3 Gas, oil,
coal
Ultraviolet (Purple
Peeper®)
C7012A,C.
Dynamic Ampli-
Check®
R7847B
e
,
h
0.8/1 or
2/3
Gas Rectifying Flame Rod
Holders
b
C7004, C7007, C7011
Complete Assemblies:
C7008, C7009, Q179
Dynamic Ampli-
Check®
R7847B
e
,
h
0.8/1 or
2/3
Oil Rectifying Photocell C7003, C7010, C7013,
C7014
d
Dynamic Ampli-
Check®
R7847B
e
,
h
2/3 Gas, oil,
coal
Ultraviolet (Purple
Peeper®)
C7012A,C
Dynamic Self-
Check
R7847C
c,f, i
2/3 Gas, oil,
coal
Ultraviolet (Purple
Peeper®)
C7012E,F
Infrared Red No R7848A 2/3 Gas, oil,
coal
Infrared (Lead
Sulfide)
C7015
Dynamic Ampli-
Check®
R7848B
e
3 Gas, oil,
coal
Infrared (Lead
Sulfide)
C7015
Ultraviolet Purple No R7849A 0.8/1 or
2/3
Gas, oil Ultraviolet
(Minipeeper)
C7027, C7035, C7044
g
Dynamic Ampli-
Check®
R7849B
d
0.8/1 or
2/3
Gas, oil Ultraviolet
(Minipeeper)
C7027, C7035, C7044
g
Dynamic Self-
Check
R7861A
c,f
0.8/1 or
2/3
Gas, oil,
coal
Ultraviolet C7061
Blue Dynamic Self-
Check
R7886A
c,f
2/3 Gas, oil,
coal
Ultraviolet (Adjustable
Sensitivity)
C7076
Optical White Dymanic Ampli-
Check®
R7851B 0.8/1 or 2/3 Gas, oil,
coal
Optical (UV, IR,
Visible Light)
C7927, C7935, C7915,
C7962
Dynamic Self-
Check
R7851C
c
2/3 Gas, oil,
coal
Optical (UV only) C7961