Honeywell L4017 Air Cleaner User Manual


 
-_
I
TRADELINE MODELS
Tradeline models are selected and packaged to provide ease of stocking, ease of handling, and maximum re-
placement value. Tradeline model specifications are the same as those of standard models except as noted below.
L4017B Combination Fan and Limit Control.
TRADELINE MODELS AVAILABLE:
MANUAL-AUTO fan switch and 10 inch [254
L4017B Combination Fan and Limit Control.
mm] self-supporting element. Includes limit
MANUAL-AUTO fan switch, 60 inch [I524
stop adjusting tool.
mm] capillary sensing element. Includes limit
ADDITIONAL FEATURES: Tradeline pack with
stop adjusting tool and element support bracket.
cross reference label and special instruction sheet.
STANDARD MODELS
MODELS:
L4017A Combination Fan and Limit Control. Unit
has adjustable fan-on and high limit set points with
fixed limit and adjustable fan differentials. With
case and cover.
L4017B Combination Fan and Limit Control. Unit
has adjustable fan-on and high limit set points
with fixed limit and adjustable fan differentials-
with MANUAL-AUTO fan switch. With case and
cover.
ELECTRICAL RATING (amperes):
I FAN
I
LIMIT
DIA. HOLE
IN MTG SJR-
FACE FOR
DIRECT IN-
120v 240V 12QV
24QV
AC
AC
AC AC
Full Load 14 7 8 4
Locked Rat&. 84 42 48 24
0.25 amp at 0.25 to 12V dc (limit only).
Maximum connected load- 2000 VA.
MAXIMUM AMBIENT TEMPERATURE: 190 F [ 88 C]
at switches and 300 F [ 149 C] at sensing element.
LIMIT DIFFERENTIAL: Fixed at 25 F [ 14 C].
SWITCH ACTION: Fan switch makes at set point
(adjustable differential model) and limit switch breaks
at set point on temperature rise. Fan switch breaks at
set point on model with fixed differential on tempera-
ture fall.
FIG. I-L4017A AND B DIMENSIONS, IN INCHES
[MILLIMETERS IN BRACKETS], AND LO-
CATjON OF MOUNTING HOLES.
(continued on page 3)
WHOLESALER OR YOUR DISTRIBUTOR, REFER TO THE TRADELINE CATALOG OR PRICE SHEETS FOR
COMPLETE ORDERING NUMBER.
SPECIFY-
4. OPTIONAL SPECIFICATION, IF DESIRED.
1. MODEL NUMBER, TRADELINE IF DESIRED.
5. FAHRENHEIT OR CELSIUS SCALEPLATE
2. SELF-SUPPORTING ELEMENT OR CAPILLARY.
AND RANGES, IF DESIRED.
3. CAPILLARY LENGTH (CAPILLARY MODELS ONLY). 6. ACCESSORY, IF DESIRED.
IF YOU HAVE ADDITIONAL QUESTIONS, NEED FURTHER INFORMATION, OR WOULD LIKE TO COMMENT ON OUR
PRODUCTS OR SERVICES, PLEASE WRITE OR PHONE:
I. YOUR LOCAL HONEYWELL RESIDENTIAL DIVISION SALES OFFICE (CHECK WHITE PAGES 0~ PHONE DlR~cT0Ryb
2. RESIDENTIAL DIVISION CUSTOMER SERVICE
HONEYWELL INC., 1885 DOUGLAS DRIVE NORTH
MINNEAPOLIS, MINNESOTA 55422 (612) 542-7500
(IN CANADA-HONEYWELL CONTROLS LIMITED, 740 ELLESMERE ROAD, SCARBOROUGH, ONTARIO MIP 2VB)
INTERNATIONAL SALES AND SERVICE OFFICES IN ALL PRINCIPAL CITIES OF THE WORLD.