Heatiator HEIR36T Indoor Fireplace User Manual


 
34
Heatilator • HEIR36, HEIR42, HEIR50 • 2285-900 Rev. D • 8/12
A*
B
10 in.
12 in.
DO NOT PACK WITH
INSULATION OR OTHER
MATERIAL
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
• Between ceiling restops
• Between wall shield restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause overheating and re.
8
8
Vent Clearances and Framing
Figure 8.2 Wall Penetration
* Shows center of vent framing hole with minimum vertical for top venting. The
center of the hole is one (1) in. (25.4 mm) above the center of the horizontal
vent pipe.
Figure 8.1 Horizontal Venting Clearances To Combustible
Materials
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184
mm) thick.
,f wall thickness is less than 4 in. the e[isting heat shields must be field trimmed. ,f
wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
,f wall thickness is less than 4-3/8 the e[isting heat shields must be field trimmed.
,f wall thickness is greater than 7-/8 in. a DVP-HSM-B will be required.
(DVP Pipe Shown)
3 in. (76 mm)
top clearance *
1 in. (2 mm)
clearance
bottom & sides
Heat
Shield
Wall
Shield
Firestop
Heat
Shield
WALL
3 in. (76 mm)
top clearance
1 in. (2 mm)
clearance around
vertical sections
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield restop(s). The wall shield
restop maintains minimum clearances and prevents cold
air in ltration.
• The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
DVP pipe - A wall shield restop is required on one side
only on interior walls. If your local inspector requires a
wall shield restop on both sides, then both wall shield
restops must have a heat shield (refer to Section
16.B.) attached to them.
• See Section 10.H. for information for regarding the in-
stallation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-com-
bustible materials such as concrete, a hole with diameter
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield restop is only required on one side and no heat
shield is necessary.
MODEL A* B
HEIR36 74-3/16 in. 73-3/16 in.
HEIR42 79-3/16 in. 78-3/16 in.
HEIR50 83-3/16 in. 82-3/16 in.