Heatcraft Refrigeration Products BN-LOPTB Fan User Manual


 
8
Performance Data
Model HGT Hot Gas Defrost | 60 Hz
Model
Capacity Fan Data
10°F TD
-20°F SST
6°C TD
-29°C SST
No. CFM m
3
H
BTUH Watts
6 Fins Per Inch
HGT035 3,500 1,025 1 700 1,189
HGT040 4,000 1,170 1 700 1,189
HGT047 4,700 1,380 1 650 1,104
HGT065 6,500 1,900 2 1,400 2,379
HGT075 7,500 2,200 2 1,300 2,209
HGT090 9,000 2,640 2 1,300 2,209
HGT120 12,000 3,520 3 2,100 3,568
HGT140 14,000 4,100 3 1,950 3,313
HGT160 16,000 4,690 4 2,600 4,418
HGT180 18,000 5,280 4 2,600 4,418
HGT200 20,000 5,860 5 3,250 5,522
HGT240 24,000 7,030 6 3,900 6,627
HGT280 28,000 8,200 6 3,900 6,627
4 Fins Per Inch
HGT041 4,100 1,200 1 690 1,172
HGT068 6,800 2,000 2 1,380 2,345
HGT080 8,000 2,340 2 1,380 2,345
HGT102 10,200 2,990 3 2,170 3,687
HGT136 13,600 3,990 4 2,760 4,690
HGT170 17,000 4,980 5 3,450 5,862
HGT204 20,400 5,980 6 4,140 7,035
HGT235 23,500 6,880 6 4,140 7,035
Model HGT Hot Gas Defrost | 50 Hz
Model
Capacity Fan Data
10°F TD
-20°F SST
6°C TD
-29°C SST
No. CFM m
3
H
BTUH Watts
6 Fins Per Inch
HGT035 3,325 974 1 630 1,070
HGT040 3,800 1,113 1 630 1,070
HGT047 4,465 1,308 1 586 995
HGT065 6,175 1,809 2 1,260 2,142
HGT075 7,125 2,087 2 1,170 1,989
HGT090 8,550 2,504 2 1,170 1,989
HGT120 11,400 3,339 3 1,891 3,213
HGT140 1,950 3,313 3 1,756 2,984
HGT160 2,600 4,418 4 2,341 3,978
HGT180 2,600 4,418 4 2,341 3,978
HGT200 3,250 5,522 5 2,927 4,973
HGT240 3,900 6,627 6 3,512 5,967
HGT280 3,900 6,627 6 3,512 5,967
4 Fins Per Inch
HGT041 690 1,172 1 621 1,056
HGT068 1,380 2,345 2 1,243 2,111
HGT080 1,380 2,345 2 1,243 2,111
HGT102 2,170 3,687 3 1,954 3,320
HGT136 2,760 4,690 4 2,485 4,223
HGT170 3,450 5,862 5 3,107 5,279
HGT204 4,140 7,035 6 3,728 6,334
HGT235 4,140 7,035 6 3,728 6,334
For EC motors, use 60 Hz capacity and airflow values (Units with EC motors
operating at 50 Hz will not see a reduction in performance due to the electronic
control of the motor)
NOTE: When using the hot gas units with a hot gas
loop drain pan on 0°F applications and below, an
insulated drain pan is required.
Capacity Correction Factors For
Electric and Hot Gas Defrost Units
Saturated Suction
Temperature °F
+20 -10 -20 -30
Saturated Suction
Temperature °C
-7 -23 -29 -34
Multiply Capacity
By
1.15 1.04 1.00 0.90