Heatcraft Refrigeration Products BN-LOPTB Fan User Manual


 
4
Performance Data
Model ADT Air Defrost | 60 Hz
Model
Capacity Fan Data
10°F TD
25°F SST
6°C TD
-4°C SST
No. CFM m
3
H
BTUH Watts
ADT040 4,000 1,170 1 730 1,240
ADT052 5,200 1,520 1 700 1,189
ADT065 6,500 1,900
1 650 1,104
ADT070 7,000 2,050 2 1,460 2,481
ADT090 9,000 2,640 2 1,400 2,379
ADT104 10,400 3,050 2 1,400 2,379
ADT120 12,000 3,500 2 1,300 2,209
ADT130 13,000 3,810 2 1,300 2,209
ADT140 14,000 4,100 3 2,100 3,568
ADT156 15,600 4,570 3 2,100 3,568
ADT180 18,000 5,270 3 1,950 3,313
ADT208 20,800 6,100 4 2,800 4,758
ADT260 26,000 7,620 5 3,250 5,522
ADT312 31,200 9,140 6 3,900 6,627
ADT370 37,000 10,840 6 3,900 6,627
Model ADT Air Defrost | 50 Hz
Model
Capacity Fan Data
10°F TD
25°F SST
6°C TD
-4°C SST
No. CFM m
3
H
BTUH Watts
ADT040 3,800 1,112 1 670 1,117
ADT052 4,940 1,445 1 630 1,070
ADT065 6,175 1,807 1 586 995
ADT070 6,650 1,946 2 1,315 2,234
ADT090 8,550 2,502 2 1,260 2,142
ADT104 9,880 2,891 2 1,260 2,142
ADT120 11,400 3,335 2 1,170 1,989
ADT130 12,350 3,613 2 1,170 1,989
ADT140 13,300 3,891 3 1,891 3,213
ADT156 14,820 4,336 3 1,891 3,213
ADT180 17,100 5,003 3 1,756 2,984
ADT208 19,760 5,781 4 2,521 4,284
ADT260 24,700 7,226 5 2,927 4,973
ADT312 29,640 8,672 6 3,512 5,967
ADT370 35,150 10,284 6 3,512 5,967
For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will
not see a reduction in performance due to the electronic control of the motor)