B. Installing Vent Components
1. Attach the First Vent Component to the
Starting Collars
To attach the first vent component to the starting
collars of the fireplace:
Apply a 3/8 inch (9.5 mm) bead of stove cement
around the 5 inch (127 mm) fireplace starting collar.
Make sure that the fireplace rope gasket supplied
with the fireplace seals between the first
8-5/8 inch (219 mm) vent component and the outer
fireplace wrap.
Lock the vent components into place by sliding the
concentric pipe sections with four (4) equally
spaced interior beads into the fireplace collar or
previously installed component end with four (4)
equally spaced indented sections.
When the internal beads of each 8-5/8 inch
(219 mm) outer pipe line up, rotate the pipe section
clockwise about one-quarter (1/4) turn. The vent
pipe is now locked together.
The first 90° elbow installed in the vent system of a
rear venting fireplace MUST BE in a vertical posi-
tion.
1. Apply the stove ce-
ment.
2. Line up the internal
beads and rotate the
pipe sections clock-
wise until locked.
3. Lock the vent compo-
nents into place.
4. Check the seal on the
rope gasket.
Figure 10. Attaching the First Vent Component to
the Starting Collars
WARNING
A 3/8 INCH (9.5 MM) BEAD OF STOVE
CEMENT MUST BE PLACED AROUND
THE 5 INCH (127 MM) FIREPLACE
STARTING COLLAR BEFORE
ATTACHING THE FIRST VENT
COMPONENT. FAILURE TO SEAL THIS
JOINT MAY CAUSE THE FIREPLACE TO
OPERATE IMPROPERLY. SEE THE
DIAGRAM .
STARTING
COLLAR
STARTING
COLLAR
FIRST
VENT
COMPONENT
FIRST
VENT
COMPONENT
STOVE
SEALANT
BEAD
3/8" (9.5 mm)
STOVE
SEALANT
BEAD
3/8" (9.5 mm)
1 INCH (25.4 mm)
3/8 INCH (9.5 mm)