Heat Controller VMC24SB-1/VMH24SB-1 Heat Pump User Manual


 
- 23 -
Only for training and service purposes
Part 2 Functions & Controls
5.9 Total Current Control (Over Current Protection)
5.9.1 9,12kBtu/h Model
1) CT1 control
If the operating current reaches CT1, the operating frequency of the compressor decreases.
After decreasing the operating frequency by 4Hz, if operating current is below I1 for 60 seconds continuously, the
operating frequency of compressor increases to setting frequency.
2) CT2 control
If the operating current of the appliance reaches CT2, the compressor stops instantly and two minutes later the com-
pressor restarts again.
If CT2 occurs 5 times within one hour, the appliance turns off and displays ERROR CODE 7.
Model CT 1 CT 1
CT 2
(kBtu/h) (Cooling) (Heating)
9 7.5A 9A 10A
12 7.5A 9A 10A