Heat Controller B-MMH09FA-1 Air Conditioner User Manual


 
- 40 -
Wall Mounted Multi-Zone Split System Air Conditioner
Test Running
1. Check that all copper piping and wiring has been proper-
ly connected.
2. Check that the gas and liquid side service valves are
fully open.
1) Prepare remote controller
Remove the battery cover by pulling it according to
the arrow direction.
Insert new batteries making sure that the (+) and (–)
of battery are installed correctly.
Reattach the cover by pushing it back into position.
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
• Remove the batteries from the remote controller if the sys-
tem is not going to be used for a long time.
2) Precautions in test run
The initial power supply must provide at least 90% of
the rated voltage.
Otherwise, the air conditioner should not be operated.
First operate the unit in cooling, even if you are test-
ing the unit in the winter/heating season.
Operating the unit in heating first during the test run
can cause compressor trouble.
Carry out the test run more than 5 minutes without
failure. (Test run will be cancelled 18 minutes later
automatically)
The test run is started by pressing timer cancel button
five times continuously.
To cancel the test run, press any button.
3) Settlement of outdoor unit
Anchor the outdoor unit with a bolt and
nut(ø10mm/0.4inch) tightly and horizontally on a con-
crete or rigid mount.
When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
If the vibration from the unit is being transferred to
the indoor unit via the connection of the condensation
hose and/or copper tubing, secure the outdoor unit with
anti-vibration rubber grommets.
4) Evaluation of the performance
Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of
air.
3. Ensure the difference between the intake temperature
and the discharge is more than 8°C(14.4°F) (Cooling) or
reversely (Heating).
Bolt
Tubing connection
Split Type
Discharge
temperature
Discharge air
Intake temperature
R-410A 35°C (95°F) 8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
Test Running