Hearth and Home Technologies SL-750TR-E Indoor Fireplace User Manual


 
Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. L • 11/0830
Figure 7.7
Note: If installing a vertical vent/termination off the top of
the appliance, the optional vertical termination baf e may
be needed.
V
1
V
1
= 60 ft. Max. (18.3 m)
Top Vent - Vertical Termination
No Elbows
Note: Use SLP Series
components only.
EXHAUST BAFFLE
Figure 7.8
Top Vent Application
To access the exhaust
openings, remove the ex-
haust baf e. To remove
exhaust baf e, remove
the two wing nuts.
Rear Vent Application
Note: Be sure to rein-
stall the exhaust baf e
after exhaust restrictor
installation.
Exhaust restrictor Instructions
1. Install the exhaust restrictor over the center of the ex-
haust outlet in the rebox (see Figure 7.8).
2. Center the exhaust restrictor in the open end of the
exhaust outlet and secure through the slots on the ex-
haust restrictor with the 2-1/4 in. self tapping screws
provided in the appliance manual bag.
Exhaust restrictor
Exhaust restrictor
Exhaust restrictors are recommended for these vertically
terminated products which have excessive draft. Exhaust
restrictors will compensate for high draft, and restore vi-
sual ame height. If the vent con guration has a total
vertical of 15-60 feet, an exhaust restrictor may be need-
ed. The exhaust restrictor can be located in the appliance
manual bag.