Hearth and Home Technologies RUTHERFORD-42 Indoor Fireplace User Manual


 
20
D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
Observe all required air space clearances to combustible materials as shown in Figure 6.2.
18 1/2 in.
[470 mm]
19 3/4 in.
[500 mm]
4 in.
[102 mm]
50° angle
39° angle
24 in.
[610 mm]
BRICK
FRONT
FLUSH
FRONT
24 in.
[610 mm]
22 3/8 in.
[568 mm]
52-7/8 in.
(1343 mm)
42 in.
[1067 mm]
Note: Grid depicts 1 inch squares.
Figure 6.3 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)
B
C
A
2 in. (51 mm)
min. air space
clearance
from chimney.
Note: Framing must be
extended straight up,
all the way to the ceiling.
Header MUST NOT be notched!
D
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.
D
Figure 6.4 Framing the Fireplace
C. Sidewalls/Surrounds
Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from replace opening.
Mantle leg, surround, stub wall, whether combustible or noncombustible, may be constructed as shown in Figure 6.3.
Model # A B * C ** D
RUTHERFORD-42 in. 53 7/8 28 3/8 74 1/2 12
mm 1368 721 1892 305
* If interior of chase will be drywalled, add the thickness to this meaurement.
** Adjust header height for raised oor under replace.
Heat & Glo • RUTHERFORD-42 • 4059-309 Rev G • 11/08