Hearth and Home Technologies I80 Indoor Fireplace User Manual


 
44
E. Combustible Mantel
See Figure 11.11.
A combustible mantel may be positioned no lower than
12 in./305 mm (I60) or 20 in./508 mm (I80) above the
top of the replace opening.
A combustible mantel may have a maximum depth of
12 in./305 mm.
Combustible trim and materials cannot be placed within
6 in. (152 mm) of the replace opening (top or sides).
Combustible materials projecting more than 1-1/2 in.
(38 mm) shall not be placed within 12 in. (305 mm) from
the top of the replace opening.
Combustible trim must not cover the metal surfaces of
the replace.
Mantel clearance is in accordance with Section 7-3.3.3
of ANSI/NFPA211.
12 in.
(305 mm)
55-1/2 in.
(1410 mm)
Effective
Height
*
Top of
Fireplace
Opening
* I60 12 in./305 mm
I80 20 in./504 mm
Figure 11.11 Clearances to Mantels or other Combustibles above
Fireplace
Heatilator • I60, I80 • 4013-250 • Rev C • 11/08