Hearth and Home Technologies EM-415 Indoor Fireplace User Manual


 
Heat & Glo • EM-415/EM-415H • 31317 Rev Q • 10/06
17
A. Chimney Requirements
Vertical distances are measured from the base of the re-
place as shown in Figure 5.2.
To determine the chimney components needed to complete
your particular installation, follow the steps below:
Determine the total vertical height of the fireplace
installation. This dimension is measured from the base of
the replace assembly to the point where the smoke exits
the termination cap.
Subtract the effective height of the replace assembly from
the overall height of the replace installation (measured
from the base of the fireplace to the bottom of the
termination cap).
Refer to Table 5.1 to determine what components must
be selected to complete the replace installation.
Determine the number of ceiling restops, stabilizers,
roof flashing, etc. required to complete the fireplace
installation.
6 ft (1.8 m) max.
unsupported
run
20 ft (6.10 m) max.
pipe between an
offset & return
Ceiling firestop
35 ft (10.7 m)
max. straight
unsupported
chimney height
16.5 ft (5.03 m) min. height/single offset-return
20 ft. (6.10 m) min. height/double offset-return
90 ft (27.4 m) max. height
6 ft (1.83 m) max.
unsupported chimney
above roof
41-1/4 in.
(1048 mm)
Effective
Height
Figure 5.2 Chimney Requirements
Table 5.1
Do NOT connect this fireplace to a chimney flue
servicing another appliance.
Do NOT connect to any air distribution duct or
system.
CAUTION
Fire Risk
Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.
WARNING
HEIGHT OF CHIMNEY COMPONENTS in. mm
Chimney Stabilizer
SL3 4-3/4 121
Ceiling Firestops
FS338 0 0
FS339 0 0
FS340 0 0
Offsets/Returns
SL315 13-3/8 340
SL330 15-1/2 394
Roof Flashing
RF370 0 0
RF371 0 0
Chimney Sections*
SL306 4-3/4 121
SL312 10-3/4 273
SL318 16-3/4 425
SL324 22-3/4 578
SL336 34-3/4 883
SL348 46-3/4 1187
* Dimensions re ect effective height.
Minimum overall straight height 16.5 ft (5.03 m)
Minimum height with offset/return 16.5 ft (5.03 m)
Maximum height 90 ft (27.43 m)
Maximum chimney length between an offset
and return
20 ft (6.10 m)
Maximum distance between chimney
stabilizers
35 ft (10.67 m)
Double offset/return minimum height 20 ft (6.1 m)
Maximum unsupported chimney length
between the offset and return
6 ft (1.83 m)
Maximum unsupported chimney height above
the replace
35 ft (10.67 m)
Maximum unsupported chimney above roof 6 ft (1.83 m)
Note: A maximum of two pairs of offsets and returns may
be used.