Hearth and Home Technologies BIR50-B Indoor Fireplace User Manual


 
24
(4) Roof
Radiation
Shields
Chimney Section
Chimney Section
Attic Insulation
Shield & Collar
Square Frame
Firestop
Square Frame
Firestop
Chimney Section
74 1/8 in.
(1883 mm)
Effective
Height
Termination
Cap
Storm
Collar
Chase Top
Flashing
Figure 8.1
Determine the chimney components needed to complete
your particular installation:
Measure the total vertical height of the replace installation
from the base of the replace assembly to the approximate
location of the bottom of the termination cap.
Subtract the effective height of the replace assembly (see
Figure 8.1) from the total vertical height to determine the
overall height of the chimney installation.
Create a schematic for your application similar to Figure
8.1 showing components required (referring to Table
8.1).
Install a ceiling restop whenever the chimney penetrates
a oor/ceiling.
NOTICE: A maximum of two offset and return may be
used.
CAUTION! Risk of Fire and/or Asphyxiation! DO NOT
connect this replace to a chimney ue servicing another
appliance. Do NOT connect to any air distribution duct
or system. These actions could cause overheating/re
in the chimney ue, or release of exhaust fumes into the
living areas.
Heatilator • Birmingham BIR50-B • 4059-682C • 8/12