Hearth and Home Technologies BIR42-B Indoor Fireplace User Manual


 
20
D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
Observe all required air space clearances to combustible materials as shown in Figure 6.2.
18 1/2 in.
[470 mm]
19 3/4 in.
[500 mm]
4 in.
[102 mm]
50° angle
39° angle
24 in.
[610 mm]
BRICK
FRONT
FLUSH
FRONT
24 in.
[610 mm]
22 3/8 in.
[568 mm]
52-7/8 in.
(1343 mm)
42 in.
[1067 mm]
Note: Grid depicts 1 inch squares.
Figure 6.3 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)
Figure 6.4 Framing the Fireplace
C. Sidewalls/Surrounds
Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from replace opening.
Mantle leg, surround, stub wall, whether combustible or non-combustible, may be constructed as shown in Figure 6.3.
B
C
A
2 in. (51 mm)
min. air space
clearance
from chimney.
Header MUST NOT be notched!
D
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.
D
A B * C ** D
in.
mm
305
28 3/8
74 1/2
18927211368
12
Model #
* If interior of chase will be drywalled, add the thickness to this meaurement.
** Adjust header height for raised floor under fireplace.
Bir 42-B
The fireplace header cannot be positioned until
after the fireplace assembly is in place.
Framing must be extended straight up, all
the way to the ceiling.
53 7/8
Heatilator • Birmingham BIR42-B • 4059-681 • 11/11