Harman Stove Company 3-90-70738 Stove User Manual


 
11
WATER COIL OPTION
Example 1: Thermo-siphon Method. This is the simplest and most economical method, providing the existing
water heater (storage tank) is within 10 feet of the stove. The water inlet, where the Temp/Pressure relief valve
is located, must be higher than the top leg of the water coil. The storage tank should be elevated, if necessary,
to allow for proper thermo-siphon action.
A). Turn off the water heater and the water supply to it. Drain the tank completely.
B). Remove the Temp/Pressure relief valve and discard. Install a short ¾” nipple and tee (1) along with a new
Temp/Pressure relief valve.
C). Run ¾” copper tubing, along with the necessary ttings, between the storage tank and the top leg of the
coil. Install a ¾” vent elbow and automatic “oat type” air vent (2) in the high point of the line. Within two feet
of the top leg of the coil, install a 150 lb. pressure relief valve (7). Run ¾” tubing from the release exit of both
relief valves, downward (3) so that the hot water may escape in the event of over-heating.
D). Remove the drain valve, at the bottom of the storage tank. Install a ¾” nipple and tee, and reinstall the
drain valve to the tee (4). Run ¾” copper tubing, with the necessary ttings, between the drain/tee combination
and the lower leg of the coil.
After all of the connections are com-
pleted, you can rell the tank. Restore
power to the water heater ONLY after
the tank has been completely relled.
Example 2: Circulating pump method.
Used when the distance is more than
ten feet or when the stove is on a higher
level than the existing water heater. In
addition to a circulator, you may want
to add a aquastat to control the pump
according to water temperature. This is
not necessary if the circulator is left run
continuously. Another option is a gate valve placed near the circulator to control the rate of ow.
A). Turn off the water heater and the water supply to it. Drain the tank completely.
B). Remove the Temp/Pressure relief valve and discard. Install a short ¾” nipple and tee (1) along with a new
Temp/Pressure relief valve.
C). Remove the drain valve, at the bottom of the storage tank. Install a ¾” nipple and tee, and reinstall the
drain valve to the tee (4).
D). Install a circulating pump (6) as shown. Run ¾” copper tubing from the circulator to the lower leg of the coil.
This is where the optional gate valve (5) can be installed.
E). Install a ¾” tee and a 150 lb. pressure relief valve (7) in the top leg within 2 feet of the top outlet of the wa-
ter coil.
F). Complete the copper line by running it back to the tee at the top of the water tank, making sure to install a
vent elbow and automatic air vent (2) at the high point of the line. The optional aquastat can be installed in this
line a maximum of six feet from the stove. The aquastat must be a “close on temperature rise” type and must
be wired and set to turn on the circulator when the water temperature reaches 120˚ Farenheit.
The system is now ready to be relled and power restored to the water heater ONLY after the tank is lled.
EXAMPLE 2: Circulator
Method. (more than 10 feet.)