Harbor Freight Tools 93532 Fan User Manual


 
SKU 93532 For technical questions, please call 1-800-444-3353. Page 6
ous drop in voltage, resulting in loss of power and possible fan damage.
(See Table A.)
The smaller the gauge number of the wire, the greater the capacity of the cord. 3.
For example, a 14 gauge cord can carry a higher current than a 16 gauge cord.
(See Table A.)
When using more than one extension cord to make up the total length, make sure 4.
each cord contains at least the minimum wire size required. (See Table A.)
If you are using one extension cord for more than one fan, add the nameplate5. am-
peres and use the sum to determine the required minimum cord size.
(See Table A.)
If you are using an extension cord outdoors, make sure it is marked with the sufx 6.
“W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.
Make sure your extension cord is properly wired and in good electrical condition. 7.
Always replace a damaged extension cord or have it repaired by a qualied electri-
cian before using it.
Protect your extension cords from sharp objects, excessive heat, and damp or wet 8.
areas.
RECOMMENDED MINIMUM WIRE
GAUGE FOR EXTENSION CORDS*
(120/240 VOLT)
NAMEPLATE
AMPERES
(at full load)
EXTENSION CORD
LENGTH
25’
50’
75’
100’
150’
0 – 2.0 18 18 18 18 16
2.1 – 3.4 18 18 18 16 14
3.5 – 5.0 18 18 16 14 12
5.1 – 7.0 18 16 14 12 12
7.1 – 12.0 18 14 12 10 -
12.1 – 16.0 14 12 10 - -
16.1 – 20.0 12 10 - - -
TABLE A
* Based on limiting the line
voltage drop to ve volts at
150% of the rated amperes.
Symbology
Double Insulated
Canadian Standards Association
Underwriters Laboratories, Inc.
V~
Volts Alternating Current
A
Amperes
n
0
xxxx/min.
No Load Revolutions per Minute
(RPM)