2. Operation Details
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPERATURE +0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than More than
3 minutes 3 minutes
Selecting Selecting Selecting
fan speed fan speed fan speed
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN Low Low
(1) The function of main control
Thermal ON Thermal OFF
Indoor Unit mode ST+0.5 ST-0.5
2TH (Remo.+Indoor)
To be selected higher temperature To be selected higher temperature
contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. Mode ST+0.5 ST-0.5