Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.
25 °C
27 °C
35 °C
30 °C
22 °C
Pipe
temperature
OFF
Indoor fan
speed
LO
LOW
LOW
SELECTED
FAN
LOW
LOLOW
COMP ON
Operation Detail
Thermal
OFF
ON
OFF ON
ON
ON
Outdoor fan
Indoor fan
4 Way ON
Room
Temperature
Thermal Off
Thermal On
Indoor pipe
Temperature
33(39)°C
25°C
22(20)°C
36(42)°C
Minimum
3min
Setting
fan
speed
Setting
fan
speed
Setting
fan
speed
Stop Low
Stop StopLow
LowLow Low
Thermal ON Thermal OFF
Indoor Unit mode ST+2 ST+4
2TH To be selected lower temperature To be selected lower temperature
(Remo.+Indoor) contrast Indoor Unit and Remo. contrast Indoor Unit and Remo.
Remo. mode ST+0 ST+2