Haier AC522AFERA Air Conditioner User Manual


 
18
Installation of Indoor Unit
DRAIN PIPING
Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or
traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25)[outside diameter 38 mm.]
During installation of the drain pipe,be careful to avoid applying pressure to the drain
point of the unit.
When the pipe is long,install supporters(Fig 11).
Do not perform air bleeding.
Always heat insulate (8mm or over thick) the indoor side of the drain pipe.
BAD
GOOD
BAD
Supporter
5 to 6.5 ft
(1.5 to 2m)
Fig. 11