Haier AC182XCERA Air Conditioner User Manual


 
15
Installation Procedures
ELECTRICAL WIRING
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
(2) Pull out the electric component box.
(3) Remove the electric component box cover.
Remove the three tapping screws.
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the
dimensions shown in Fig.34.
(3) Connect the end of the connection cord fully into the
terminal block.
(4) Wiring
(4) Fasten the connection cord with a cord clamp.
(5) Fasten the end of the connection cord with the
screw.
Be careful not to pinch the lead wires between the
electric component box and base.
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection
cord with the cord clamp.(If the insulator is chafed,
electric leakage may occur.)
(4) Always connect the ground wire.
Do not remove the screws. If the screws
are removed, the electric component box
will fall.
Fig. 26
Electric component box
Remove the four tapping
screws.
Fig. 27
Electric component box
CAUTION
Fig.28
Electric component box
Fig. 29
Base
Electric component box cover
CAUTION