Goodmans GSC13 Air Conditioner User Manual


 
produCt SpeCifiCationS
produCt SpeCifiCationS
4 www.goodmanmfg.com SS-GSCC
GSC10 CommerCial produCt SpeCifiCationS
GSC10
0903A*
GSC10
0904AC
GSC10
1203A*
GSC10
1203B*
GSC10
1204B*
Cooling Capacities
Nominal Cooling (BTU/h) 87,000 87,000 109,000 114,000 109,000
EER/IEER 11.2/11.5 11.2/11.5 11.2/--- 11.2/11.2 11.2/11.2
Decibels 84 84 84 84 84
Compressor
RLA / LRA 25.6 / 196 12.8 / 100 30.1 / 225 30.1 / 225 15.5/ 114
Type Scroll Scroll Scroll Scroll Scroll
Condenser Fan Motor
Horsepower 1 1 1 1 1
FLA 5.6 3.5 5.6 5.6 3.5
Refrigeration System
Liquid Valve Size (“O.D.) ⅝" ⅝" ⅝" ⅝" ⅝"
Sucon Valve Size (“O.D.) (7½ tons) 1⅜" 1⅜" 1⅜" 1⅜" 1⅜"
Sucon Valve Size (“O.D.) (10 tons) 1⅝" 1⅝" 1⅝" 1⅝" 1⅝"
Refrigerant Charge 35 35 35 35 35
Valve Type Sweat Sweat Sweat Sweat Sweat
Electrical Data
AC Volts/ Hz 208-230/ 60 460/ 60 208-230/ 60 460/ 60
Min. Circuit Ampacity ¹ 37.6 19.5 43.2 43.2 22.9
Max. Overcurrent Device ² 60 30 70 70 35
Min / Max Volts 197/253 414/ 506 197/253 197/253 414/ 506
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Ship Weight (lbs) 315 315 334 334 334
¹ Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
³ Installer will need to supply ¾” to ⅞” adapters for sucon line connecons.
4
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Notes
Always check the S&R plate for electrical data on the unit being installed.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.