COOLING PERFORMANCE DATA
5MM COILS
GPC1342H41AB
MODEL: GPC1342H41A*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67 715963677159636771
MBh 40.2 41.6 45.6 - 39.2 40.7 44.6 - 38.3 39.7 43.5 - 37.4 38.7 42.4 - 35.5 36.8 40.3 - 32.9 34.1 37.3 -
S/T 0.77 0.65 0.45 - 0.80 0.67 0.46 - 0.82 0.69 0.48 - 0.85 0.71 0.49 - 0.88 0.74 0.51 - 0.89 0.74 0.51 -
Delta T181612 - 181612 - 181612 - 18 16 12 - 181612 - 171511 -
1580 KW 2.77 2.83 2.91 - 2.97 3.03 3.12 - 3.14 3.20 3.30 - 3.29 3.36 3.46 - 3.42 3.49 3.60 - 3.53 3.60 3.72 -
AMPS 12.3 12.5 12.9 - 13.1 13.4 13.7 - 14.0 14.3 14.7 - 14.8 15.1 15.6 - 15.6 16.0 16.4 - 16.4 16.8 17.3 -
HI PR 225 242 256 - 252 272 287 - 287 309 326 - 327 352 372 - 368 396 418 - 406 437 462 -
LO PR 110 117 128 - 117 124 135 - 121 129 141 - 127 135 148 - 133 142 155 - 138 147 160 -
MBh 39.0 40.4 44.3 - 38.1 39.5 43.3 - 37.2 38.5 42.2 - 36.3 37.6 41.2 - 34.5 35.7 39.1 - 31.9 33.1 36.3 -
S/T 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.78 0.66 0.45 - 0.81 0.68 0.47 - 0.84 0.70 0.49 - 0.85 0.71 0.49 -
Delta T191612 - 191612 - 191612 - 19 17 13 - 191612 - 181512 -
70 1410 KW 2.75 2.81 2.89 - 2.95 3.00 3.09 - 3.12 3.18 3.27 - 3.27 3.33 3.43 - 3.39 3.46 3.57 - 3.50 3.58 3.69 -
AMPS 12.2 12.5 12.8 - 13.0 13.3 13.6 - 13.9 14.2 14.6 - 14.7 15.0 15.4 - 15.5 15.8 16.3 - 16.3 16.6 17.1 -
HI PR 223 240 253 - 250 269 284 - 284 306 323 - 324 348 368 - 364 392 414 - 402 433 457 -
LO PR 109 116 127 - 115 123 134 - 120 128 139 - 126 134 146 - 132 140 153 - 137 145 159 -
MBh 36.0 37.3 40.9 - 35.2 36.4 39.9 - 34.3 35.6 39.0 - 33.5 34.7 38.0 - 31.8 33.0 36.1 - 29.5 30.5 33.5 -
S/T 0.71 0.59 0.41 - 0.74 0.62 0.43 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.68 0.47 - 0.82 0.68 0.47 -
Delta T191612 - 191713 - 191713 - 19 17 13 - 191713 - 181512 -
1240 KW 2.69 2.74 2.82 - 2.88 2.94 3.02 - 3.04 3.11 3.20 - 3.19 3.25 3.35 - 3.31 3.38 3.49 - 3.42 3.49 3.60 -
AMPS 12.0 12.2 12.5 - 12.7 13.0 13.3 - 13.6 13.9 14.3 - 14.4 14.7 15.1 - 15.2 15.5 15.9 - 15.9 16.2 16.7 -
HI PR 216 233 246 - 242 261 275 - 276 297 313 - 314 338 357 - 353 380 401 - 390 420 444 -
LO PR 106 113 123 - 112 119 130 - 116 124 135 - 122 130 142 - 128 136 149 - 132 141 154 -
MBh 40.9 42.1 45.5 48.9 39.9 41.1 44.5 47.7 39.0 40.1 43.4 46.6 38.0
39.1
42.4 45.5 36.1 37.2 40.2 43.2 33.4 34.4 37.3 40.0
S/T 0.88 0.79 0.60 0.38 0.91 0.82 0.62 0.40 0.94 0.84 0.63 0.41 0.97
0.86
0.65 0.42 1.00 0.90 0.68 0.44 1.00 0.90 0.68 0.44
Delta T21191611212016112120161121
20
16 11 21 19 16 11 19 18 15 10
1580 KW 2.79 2.85 2.93 3.02 2.99 3.05 3.14 3.23 3.16 3.23 3.32 3.43 3.32
3.38
3.49 3.60 3.45 3.52 3.63 3.74 3.56 3.63 3.75 3.87
AMPS 12.4 12.6 13.0 13.4 13.2 13.5 13.8 14.3 14.1 14.4 14.8 15.3 15.0
15.3
15.7 16.2 15.8 16.1 16.5 17.1 16.6 16.9 17.4 18.0
HI PR 227 245 258 269 255 274 290 302 290 312 330 344 330
355
375 392 372 400 422 440 411 442 467 487
LO PR 111 119 129 138 118 125 137 146 122 130 142 151 128
137
149 159 135 143 156 167 139 148 162 172
MBh 39.7 40.8 44.2 47.4 38.7 39.9 43.2 46.3 37.8 38.9 42.2 45.2 36.9
38.0
41.1 44.1 35.1 36.1 39.1 41.9 32.5 33.4 36.2 38.8
S/T 0.84 0.75 0.57 0.37 0.87 0.78 0.59 0.38 0.89 0.80 0.60 0.39 0.92
0.82
0.62 0.40 0.96 0.85 0.65 0.42 0.96 0.86 0.65 0.42
Delta T22201611222017112220171122
20
17 12 22 20 16 11 20 19 15 11
75 1410 KW 2.77 2.83 2.91 2.99 2.97 3.03 3.12 3.21 3.14 3.20 3.30 3.40 3.29
3.36
3.46 3.57 3.42 3.49 3.60 3.71 3.53 3.60 3.72 3.84
AMPS 12.3 12.6 12.9 13.3 13.1 13.4 13.7 14.2 14.0 14.3 14.7 15.2 14.8
15.1
15.6 16.1 15.6 16.0 16.4 17.0 16.4 16.8 17.3 17.8
HI PR 225 242 256 267 252 272 287 299 287 309 326 340 327
352
372 388 368 396 418 436 407 437 462 482
LO PR 110 117 128 136 117 124 135 144 121 129 141 150 127
135
148 157 133 142 155 165 138 147 160 171
MBh 36.6 37.7 40.8 43.8 35.8 36.8 39.9 42.8 34.9 35.9 38.9 41.8 34.1
35.1
38.0 40.7 32.4 33.3 36.1 38.7 30.0 30.9 33.4 35.8
S/T 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.37 0.86 0.77 0.58 0.37 0.89
0.79
0.60 0.39 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
Delta T22201711222017122220171222
21
17 12 22 20 17 12 21 19 16 11
1240 KW 2.71 2.76 2.84 2.93 2.90 2.96 3.04 3.14 3.07 3.13 3.22 3.32 3.22
3.28
3.38 3.48 3.34 3.41 3.51 3.62 3.45 3.52 3.63 3.74
AMPS 12.0 12.3 12.6 13.0 12.8 13.1 13.4 13.8 13.7 14.0 14.4 14.8 14.5
14.8
15.2 15.7 15.3 15.6 16.0 16.5 16.0 16.4 16.8 17.4
HI PR 218 235 248 259 245 264 278 290 279 300 317 330 317
341
360 376 357 384 406 423 394 424 448 467
LO PR 107 114 124 132 113 120 131 140 117 125 136 145 123
131
143 153 129 138 150 160 134 142 155 165
* IDB: Entering Indoor Dry Bulb Temperature NOTE: Shaded area is ACCA (TVA) conditions