Goodmans GPC 13 SEER R-410A Air Conditioner User Manual


 
PACKAGE COOLING SPECIFICATIONS
12
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
GPC13[36-42]H41AA
GPC1336H41* GPC1342H41*
COOLING
COOLING CAPACITY, BTUH 36,000 41,000
CAPACITY
SEER 13.0 13.0
UNIT
VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60
ELECTRICAL
AMPS (TOTAL) 20.06 22.2
SPECIFICATION
MINIMUM CIRCUIT AMPACITY 24.2 26.6
MAXIMUM OVERCURRENT PROTECTION
(1)
40 40
COMPRESSOR
TYPE SCROLL SCROLL
RATED LOAD AMPS 16.7 17.9
LOCKED ROTOR AMPS 79 112
CONDENSER
HORSEPOWER 1/4 1/4
FAN MOTOR
RPM 830 1075
FULL LOAD AMPS 1.5 1.4
LOCKED ROTOR AMPS 3.0 2.9
CONDENSER FAN
BLADE DIAMETER (INCHES) / # OF BLADES 22 / 4 22 / 4
CONDENSER
FACE AREA - SQ. FT. 13.4 17.0
COIL
NUMBER OF ROWS 1 1
FINS PER INCH 24 24
EVAPORATOR
HORSEPOWER - NO. OF SPEEDS 1/3 - 3 1/2 - 3
BLOWER
FULL LOAD AMPS 1.86 2.87
MOTOR
LOCKED ROTOR AMPS 3.2 4.9
MOTOR SPEED TAP - COOLING LOW LOW
RPM 1075 1075
EVAPORATOR
DIAMETER X WIDTH (INCHES) 9 x 8 10 x 8
BLOWER
RATED SCFM COOLING 1,205 1,410
MAX EXTERNAL STATIC PRESS ("w.c.) 0.5 0.5
EVAPORATOR
FACE AREA - SQ. FT. 5.2 6.2
COIL
NUMBER OF ROWS 3 4
FINS PER INCH 14 14
GENERAL
FILTER SIZE - SQ. FT. * 25 x 25 x 1 (2) 20 x 20 x 1
INFORMATION
DRAIN SIZE (INCHES) 3/4" 3/4"
EXPANSION DEVICE ORIFICE (0.065) ORIFICE (0.072)
REFRIGERANT CHARGE R-410A (Oz.) 85 105
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.
)
3/4, 1, 1-1/4 3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.) 1/2 1/2
SHIPPING WEIGHT LBS. 370 370
OPERATING WEIGHT LBS. 360 360