Goodman Mfg SS-GME8 Furnace User Manual


 
ProDuct sPeciFications
ProDuct sPeciFications
SS-GME8 www.goodmanmfg.com 3
sPeciFications
GME8
0703BXC*
GME8
0905CXC*
GME8
1155CXC*

Input¹ 70,000 90,000 115,000
Output¹ 56,000 72,000 92,000
LP Output¹ 48,000 64,000 80,000
AFUE² 80 80 80
Tons AC @ 0.5” ESP 3 5 5
Temperature Rise Range (°F) 20 - 50 35 - 65 35 - 65

Size (D x W) 10 X 8 10 X 10 10 X 10
HP 1/2 1 1
Speed 4 4 4
Vent Diameter³ 4 4 4
No. of Burners 3 4 5
Disposable Filter (in²) 290 480 480

Min. Circuit Ampacity⁴ 8.2 14.8 14.8
Max. Overcurrent Protecon⁵ 15 15 15
 130 163 167
¹ Natural Gas BTU/h: for altudes above 2,000’, reduce input rang 4% for each 1,000’ above sea level. Low-re rate is
75% of high-re rate.
² DOE AFUE based upon Isolated Combuson System (ICS).
³ Vent diameter may vary depending upon vent length. Refer to the latest edions of the Naonal Fuel Gas Code NFPA
54/ANSI Z223.1 (in the USA) and the Canada Naonal Standard of Canada, CAN/CSA B149.1 and CAN/CSA B142.2 (in
Canada).
4
Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in ac-
cordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
5
Refers to maximum recommended fuse or circuit breaker size; may use fuses or HACR-type circuit breakers of the same
size as noted.

All furnaces are manufactured for use on 115 VAC, 60 Hz, single phase electrical supply.
Gas Service Connecon ½” FPT
Important: It is required to size overcurrent protecon device and wires properly and make electrical connecons in ac-
cordance with the Naonal Electrical Code and/or all exisng local codes.