Goodman Mfg SS-CPKF50 Air Conditioner User Manual


 
P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-CPKF50 www.goodmanmfg.com 3
2 www.goodmanmfg.com SS-CPKF50
SPecificationS
      

Nominal Cooling (BTU/h) 23,600 33,000 35,000 40,000 48,000 53,000 57,000
EER¹ 9.0 9.0 9.0 9.0 9.0 9.0 9.0
Nominal Heang (BTU/h) 23,000 32,000 32,000 39,000 48,000 54,000 61,000
Decibels 78 78 78 78 78 80 80

RLA 12.2 17.9 5.3 7.4 9.0 9.0 10.9
LRA 64 97.4 42 50 65.5 74 101
Volts 220-240 220-240 380-420 380-420 380-420 380-420 380-420

Horsepower ¼ ¼ ¼
FLA 0.9 0.9 1.2 0.8 1.2 1.2 1.2
Volts 220-240 220-240 380 380 380 380 380

Liquid Valve Size (“O.D.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Sucon Valve Size (“O.D.) ¾ ¾ ¾
Valve Type Sweat Sweat Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge (oz.) 72 110 110 131 137 138 167
Shipped with Orice Size (in.) 0.059 0.073 0.073 0.080 0.084 0.093 0.093

Horsepower - RPM ¼-950 ¼-950 ⅓-1075 ¼-950 ⅓-1075 ⅓-1075 ⅓-1075
Fan Diameter/ # Fan Blades 20/3 20/3 20/3 22/3 22/3 22/3 22/3
Outdoor Nominal CFM 1800 1800 1800 2600 2600 2600 3200
Face Area (²) 13.3 14.58 14.58 14.58 17 17 1
Rows Deep/ Fins per Inch 1/19 1/19 1/19 1/19 1/19 1/22 1/22
Fin Type Ripple Ripple Ripple Ripple Ripple Ripple Ripple
Coil No. of Tubes 22 24 24 24 24 36 36
Coil Tube Diameter (in.) 0.375 0.375 0.375 0.375 0.375 0.375 0.375

Voltage-Hz / Phase 220/240-50/1 380/415-50/3
Min. Circuit Ampacity² 16.2 23.3 7.9 10 12.4 12.4 14.8
Max. Overcurrent Protecon ³ 25 amps 40 amps 15 amps 15 amps 20 amps 20 amps 25 amps
Min / Max Volts 198/264 198/264 342/456 342/456 342/456 342/456 342/456
Power Supply Conduit Size ½ or ¾ ½ or ¾ ½ or ¾ ½ or ¾ ½ or ¾ ½ or ¾ ½ or ¾
 191 (87) 206 (94) 206 (94) 213 (97) 216 (98) 248 (113) 249 (113)
¹ Energy Eciency Rao
² Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.