SS-CPKF50 www.goodmanmfg.com 3
2 www.goodmanmfg.com SS-CPKF50
dimenSionS
H
W
D
   
CPKF24-2* 26 26 29¾
CPKF36-2/5* 26 26 32¼
CPKF42-5* 29 29 32¼
CPKF48-5* 29 29 32¼
CPKF60-5* 29 29 38¼
CPKF61-5* 29 29 38¼
Performance ratingS

-

 

  EER¹  47°F   17°F 
CPKF24-2* A24-00-2RA 23,400 16,400 9.0 2.60 23,000 2.8 7.0 12,400 2.00 78
CPKF36-2/5*
A36-00-2RA 33,000 24,100 9.0 3.67 32,000 2.9 7.2 17,400 2.00 78
A48-00-2RA 35,000 25,900 9.0 3.89 32,000 3.0 7.5 19,000 2.30 78
CPKF42-5* A48-00-2RA 40,000 30,700 9.0 4.44 39,000 3.1 7.8 21,400 2.00 78
CPKF48-5* A48-00-2RA 48,000 34,600 9.0 5.33 48,000 3.3 8.2 29600 2.30 78
CPKF60-5* A60-00-2RA 53,000 36,600 9.0 5.89 54,000 3.2 8.0 35,400 2.10 80
CPKF61-5* A60-00-2RA 57,000 38,800 9.0 6.33 61,000 3.0 8.0 37,800 2.20 80
¹ Energy Eciency Rao @ 80°F / 67°F / 95°F
² kWI = Compressor + Indoor Blower + Outdoor Fan Was
³ HSPF = Heang Seasonal Performance Factor
Note: When mix-matching outdoor and indoor units, the indoor unit check-owrator must match the outdoor unit size.
nomenclature
Product Category Engineering
C Split System Major/ Minor Revisions
Unit Type
E Commercial Air Conditioner Electrical
K Air Conditioner 1 208/230 V, 1 Phase, 60 Hz
P Heat Pump 2 220/240 V, 1 Phase, 50 Hz
3 208/230 V, 3 Phase, 60 Hz
Nominal Capacity 4 460 V, 3 Phase, 60 Hz
018 1½ Tons 048 4 Tons 5 380/415 V, 3 Phase, 50 Hz
024 2 Tons 060 5 Tons
030 2½ Tons 090 7½ tons
036 3 Tons 120 10 Tons
042 3½ Tons
PKF
2,3,4
036
5,6,7 8
1
9,101
C AA