Goodman Mfg PC50 Air Conditioner User Manual


 
P
RODUCT
S
PECIFICATIONS
SS-PC50 www.goodmanmfg.com 5
EVAPORATOR BLOWER SPECIFICATIONS
Model Speed Air ow
External Static Pressure In-Water [Mbar]
0.1 [0.25] 0.2 [0.5] 0.3 [0.75] 0.4 [1.0] 0.5 [1.25]
PC060-5A
Low CFM [L/s] 1885 [890] 1840 [870] 1795 [850] 1675 [790] 1575 [740]
High CFM [L/s] 2030 [960] 1955 [920] 1900 [900] 1760 [830] 1655 [780]
PC048-5A
Low CFM [L/s] 1540 [730] 1450 [680] 1315 [620] 1215 [570] 1070 [500]
High CFM [L/s] 1590 [750] 1490 [700] 1395 [660] 1280 [600] 1120 [530]
[ ] Designates metric measurements
Notes:
1. Data shown is dry coil. Wet coil pressure drop is approx.
2. 0.1” H2O, for two-row indoor coil; 0.2” H
2
O, for three-row indoor coil; and 0.3” H
2
O, for four-row indoor coil.
3. Data shown does not include lter pressure drop, approx. 0.08” H
2
O.
4. ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER
ASM., See Repair Parts list.
5. Reduce air ow by 2% for 208-volt operation.