Goodman Mfg PC50 Air Conditioner User Manual


 
P
RODUCT
S
PECIFICATIONS
4 www.goodmanmfg.com SS-PC50
EXPANDED COOLING RATINGS
PC048-5G
Indoor
Air
Condenser Air Temperature
75 85 95 105 115
SCFM WB
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
1194
71 48.1 23.5 4.05 46.9 23.6 4.32 45.8 23.7 4.56 43.5 23.4 4.76 40.3 21.8 4.93
67 45.0 29.5 3.92 43.9 29.5 4.18 42.8 29.7 4.41 40.7 29.3 4.60 37.7 27.3 4.77
63 42.1 33.9 3.80 41.1 33.9 4.04 40.1 34.1 4.26 38.1 33.7 4.45 35.3 31.4 4.61
59 41.2 35.3 3.71 40.2 35.4 3.96 39.2 35.6 4.17 37.3 35.1 4.35 34.5 32.8 4.50
1365
71 52.1 26.4 4.16 50.8 26.5 4.44 49.6 26.7 4.68 47.1 26.3 4.89 43.6 24.6 5.06
67 48.7 33.1 4.02 47.6 33.1 4.29 46.4 33.4 4.52 44.1 32.9 4.72 40.8 30.7 4.89
63 45.6 38.1 3.90 44.5 38.1 4.15 43.4 38.4 4.37 41.3 37.8 4.57 38.2 35.3 4.73
59 44.6 39.7 3.81 43.6 39.8 4.06 42.5 40.0 4.28 40.4 39.5 4.46 37.4 36.9 4.62
1536
71 53.6 28.6 4.20 52.4 28.6 4.47 51.1 28.8 4.72 48.5 28.4 4.93 45.0 26.5 5.11
67 50.2 35.7 4.06 49.0 35.8 4.33 47.8 36.0 4.56 45.4 35.5 4.76 42.1 33.2 4.94
63 47.0 41.1 3.93 45.9 41.1 4.19 44.7 41.4 4.41 42.5 40.9 4.61 39.4 38.2 4.77
59 46.0 42.9 3.84 44.9 42.9 4.09 43.8 43.8 4.31 41.6 41.6 4.50 38.5 38.5 4.66
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil.
For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree
below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
Total MBTU/h 43.0 Sensible MBTU/h 33.0 Latent MBTU/h 10.0
PC060-5G
Indoor
Air
Condenser Air Temperature
75 85 95 105 115
SCFM WB
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
Total
MBTU
Sens
MBTU
Watts
kWh
1481
71 56.7 27.7 5.23 55.3 27.8 5.57 54.0 28.0 5.87 51.3 27.6 6.12 47.5 25.8 6.35
67 53.0 34.7 5.06 51.8 34.8 5.39 50.5 35.0 5.68 48.0 34.5 5.92 44.4 32.2 6.13
63 49.6 39.9 4.90 48.4 40.0 5.21 47.3 40.3 5.49 44.9 39.7 5.73 41.6 37.1 5.93
59 48.6 41.7 4.79 47.4 41.7 5.10 46.2 42.0 5.37 43.9 41.4 5.60 40.7 38.7 5.80
1693
71 61.4 31.2 5.36 59.9 31.2 5.71 58.5 31.4 6.02 55.6 31.0 6.29 51.5 28.9 6.52
67 57.4 39.0 5.19 56.1 39.1 5.53 54.7 39.3 5.83 52.0 38.8 6.08 48.1 36.2 6.30
63 53.8 44.9 5.02 52.5 44.9 5.35 51.2 45.2 5.64 48.6 44.6 5.88 45.1 41.7 6.09
59 52.6 46.8 4.92 51.4 46.9 5.23 50.1 47.2 5.51 47.6 46.5 5.75 44.1 43.5 5.95
1905
71 63.2 33.7 5.41 61.7 33.7 5.76 60.2 33.9 6.08 57.2 33.5 6.34 53.0 31.3 6.57
67 59.2 42.1 5.23 57.7 42.2 5.57 56.3 42.5 5.87 53.5 41.9 6.13 49.6 39.1 6.35
63 55.4 48.5 5.07 54.1 48.5 5.39 52.7 48.8 5.68 50.1 48.2 5.93 46.4 45.0 6.14
59 54.2 50.6 4.96 52.9 50.6 5.28 51.6 51.6 5.56 49.0 49.0 5.80 45.4 45.4 6.01
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil.
For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree
below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
Total MBTU/h 50.7 Sensible MBTU/h 38.9 Latent MBTU/h 11.8